LIGHT OIL AUTOMATIC OPERATION


Light Up & Adjustment


  • Make sure all the fuel shut-off valves are kept open. Open furnace door and dampers
  • Switch ON the control panel. Start blower and check direction of rotation. Care should be taken that the discharge or the suction of the blower is closed during start-up.
  • Switch ON the Burner Ignition Push button, the following cycle starts.

    Ignition + Gas solenoid valve open PILOT FLAME ON
    Time(10S) + UV Sensor UV Flame relay ON
    UV Relay ON + Time (10S) MAIN SOLENOID VALVE ON
    Time(10S) + MAIN FLME ON IGNITION TRNSFORMER OFF
    Ignition transformer off SOLENOID VALVE OFF
    If ‘d’ fails RESET & START FROM “”

  • After burner is lit, gradually open zone air butterfly control valve till the burner has reached high fire condition. Set air/fuel ratio by adjusting the sensitrol oil valve. This is the ‘HIGH FIRE’ setting. Gradually the sensitrol valve if required. Lock the sensitrol oil valve by tightening grub screw provided on the valve bonnet. Also move indicator to sensitrol handle position. This act as high fire position indictor close the zone air butterfly valve to 1/4 or less open, loosen the spring catridge lock-nut and adjust spring cartridge of the Ratiotrol to set air fuel ratio. This is “LOW FIRE” setting. Gradually increase to high fire and adjust. The air-fuel ratio of the burner is now set.